Manual # 016-0159-894 Rev H 01/07
317
A P P E N D I X
G
TESTING THE FLOW METER CABLES
Before starting this test, disconnect the flow meter cable from the flow meter. Hold
the flow meter cable so that the keyway is pointing in the 12 o’clock position as
shown below.
Pin
Designations
and Voltage
Readings
The following tables show the following pin designations and voltage readings.
Helpful Hint: In a non-CAN system if a +5 voltage reading is not
present,disconnect the Speed Sensor cable. If the voltage reading
is restored, test the Speed Sensor cable per Appendix F - ‘Testing
the Speed Sensor Extension Cable’.
Pin Location Designation
2 o'clock Ground
10 o'clock Power
6 o'clock Signal
Pin Connections Voltage
2 o'clock to 6 o'clock +5 Volts
2 o'clock to 10 o'clock +5 Volts